Franalysis
SCPI Commands :
FRANalysis:ENABle
FRANalysis:REPeat
FRANalysis:RESet
FRANalysis:STATe
FRANalysis:MODE
- Commands in total: 86Subgroups: 17Direct child commands: 5
- get_enable() bool[source]
# FRANalysis:ENABle value: bool = driver.franalysis.get_enable()
Enables the frequency response analysis application. If the frequency response analysis is disabled, the instrument does not accept any FRANalysis command. You can start the analysis with method
RsMxo.franalysis.state().- Returns:
state: OFF | ON
- get_mode() FrAnalysisAppMode[source]
# FRANalysis:MODE value: enums.FrAnalysisAppMode = driver.franalysis.get_mode()
- Selects the application mode.
Gain/phase: Frequency response analysis (option R&S MXO5-K36)
Impedance: Impedance analysis (option R&S MXO5-K337)
- Returns:
application_md: GPHase | IMPedance
- get_repeat() bool[source]
# FRANalysis:REPeat value: bool = driver.franalysis.get_repeat()
Repeats the measurement, using the same parameters.
- Returns:
repeat: OFF | ON
- get_state() ProcessState[source]
# FRANalysis:STATe value: enums.ProcessState = driver.franalysis.get_state()
Starts the frequency response analysis.
- Returns:
value: RUN | STOP | OFF
- reset() None[source]
# FRANalysis:RESet driver.franalysis.reset()
Resets the frequency response analysis.
- reset_and_wait(opc_timeout_ms: int = -1) None[source]
# FRANalysis:RESet driver.franalysis.reset_and_wait()
Resets the frequency response analysis.
Same as reset, but waits for the operation to complete before continuing further. Use the RsMxo.utilities.opc_timeout_set() to set the timeout value.
- Parameters:
opc_timeout_ms – Maximum time to wait in milliseconds, valid only for this call.
- set_enable(state: bool) None[source]
# FRANalysis:ENABle driver.franalysis.set_enable(state = False)
Enables the frequency response analysis application. If the frequency response analysis is disabled, the instrument does not accept any FRANalysis command. You can start the analysis with method
RsMxo.franalysis.state().- Parameters:
state – OFF | ON
- set_mode(application_md: FrAnalysisAppMode) None[source]
# FRANalysis:MODE driver.franalysis.set_mode(application_md = enums.FrAnalysisAppMode.GPHase)
- Selects the application mode.
Gain/phase: Frequency response analysis (option R&S MXO5-K36)
Impedance: Impedance analysis (option R&S MXO5-K337)
- Parameters:
application_md – GPHase | IMPedance
- set_repeat(repeat: bool) None[source]
# FRANalysis:REPeat driver.franalysis.set_repeat(repeat = False)
Repeats the measurement, using the same parameters.
- Parameters:
repeat – OFF | ON
- set_state(value: ProcessState) None[source]
# FRANalysis:STATe driver.franalysis.set_state(value = enums.ProcessState.OFF)
Starts the frequency response analysis.
- Parameters:
value – RUN | STOP | OFF
Cloning the Group
# Create a copy of the original group, that exists independently
franalysis_copy = driver.franalysis.clone()
Subgroups